Configuration method
Configuration method
Configuration method
Configuration method
4-5
[1-8] Offset parameter for LCD level values
Parameter
Default Value
Description
-99.999-99.999
0.000
Parameter range, in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units
Note: Offset affects LCD display only and does not affect analog output or other values.
[2--] ANALOG Settings
[2-1] Analog output parameter
Parameter
Value
Description
0
Level
Level value converted to 4-20 mA
1
Ullage
Ullage value converted to 4-20 mA
2
Volume
Volume value converted to 4-20 mA
3
Amplitude
Signal strength amplitude value converted to 4-20 mA
[2-2] Minimum output (4 mA)
Parameter
Output
Default Value
Description
-3.000-23.000
Level
0.000
Parameter range in metric [m] units
-3.000-23.000
Ullage
0.000
Parameter range in metric [m] units
0.000-100.000
Volume
0.000
[%]
0.000-100.000
Amplitude
0.000
[dB]
When [ft] units are selected for “Level” or “Ullage” display, parameter range is calculated in ‘feet’.
[2-3] Maximum output (20 mA)
Parameter
Output
Default Value
Description
-3.000-23.000
Level
20.000
Parameter range in metric [m] units
-3.000-23.000
Ullage
20.000
Parameter range in metric [m] units
0.000-100.000
Volume
100.00
[%]
0.000-100.000
Amplitude
100.00
[dB]
When [ft] units are selected for “Level” or “Ullage” display, parameter range is calculated in ‘feet’.
[2-4] Alarm selection
Parameter
Value
Description
0
High output
22 mA alarm output
1
Low output
3.9 mA alarm output
2
Hold output
Hold last value
[2-5] Fixed current output setting
Parameter
Value
Description
0
Measuring Value
[mA]
3.900-22.000
Fixed current
Any current value selectable