Electrical Installation
Electrical Installation
Electrical Installation
Electrical Installation
3-2
3.2 Cables
Cable Use shielded twisted pair for connection.
Cross-sectional area of conductor is 0.2 …2.5mm
2
.
(AWG24 …14)
Cable entry 2
×
M20
×
1.5 (cable diameter 10mm max.)
3.3 Load
Minimum load for HART
®
250
Ω
Maximum load (Non-Ex)
900
Ω
(EX)
540
Ω
3.4 Power supply
Power (Non-Ex)
16…36VCD
(EX)
16…28VDC
3.5 Grounding
The terminal must be connected to earth ground prior to connection to any other
equipment.