Configuration method
Configuration method
Configuration method
Configuration method
4-4
4.1.4 Parameter instructions
- shaded areas indicate default settings
.
[1--] CONFIGURATION Settings
[1-1] Output Parameter: LCD display
Parameter
Value
Description
0
Level
Level value from target
1
Ullage
Distance between measuring reference point and target
2
Volume (%)
Volume rate value (%)
3
Current
Current value (mA) (4-20 mA)
4
Amplitude
Signal strength (dB)
5
Max. Volume
Max value of volume settings
When [ft] units are selected for “Level” or “Ullage” display, parameter range is calculated in ‘feet’.
[1-2] Antenna type
Parameter
Value
0
4 inch cone
1
6 inch cone
2
8 inch cone
3
Rod antenna (inactive SHORT)
4
Rod antenna (inactive LONG)
[1-3] Measuring Unit
Parameter
Value
Description
0
m
Sets display in Metric units
1
ft
Sets display in Feet units
Note: When ‘Measuring Unit’ is changed, units of other parameters also change.
[1-4] G parameter
(
distance between flange reference point and measuring reference point
)
Parameter
Default Value
Description
-3.000-3.000
0.000
R+C-G
≦
20 (
Parameter range in metric [m] units)
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[1-5] R parameter
(
Measurement range
)
Parameter
Default Value
Description
0.000-23.000
0.000
R+C-G
≦
20 (
Parameter range in metric [m] units)
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[1-6] C parameter
(
Below measurement range
)
Parameter
Default Value
Description
0.000-10.000
0.000
R+C-G
≦
20 (
Parameter range in metric [m] units)
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[1-7] H parameter
(
Deadband
)
Parameter
Default Value
Description
0.000-23.000
0.103 (4 inch cone)
0.223 (6 inch cone)
0.343 (8 inch cone)
0.350 (Rod Long)
0.500 (Rod Short)
Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units