5 Configuration
5.1 Basic settings
Set up the following parameters
- Output Parameter
Select measurement value displayed on the LCD.
- Meas. Unit
Select measurement unit, meter or feet.
- Antenna Type
Select type of antenna.
- R
Set the distance from ref. point to level zero.
- C
Set the distance from level zero to bottom of tank.
(‘C’ is normally set to ‘0’. If it is necessary to measure
negative level, please set the distance.)
- H
Set the distance from ref. point to measurement range.
(see 5.2.1)
Parameters of tank dimensions are optimized for your application.
Ref. Point
R
C
Level
Ullage
Fluid
surface
Zero Level
Bottom
H
Measuring
Range
- Analog Output Parameter
Select measurement value output for analog output.
- Minimum Output
Set value corresponding to 4mA.
- Maximum Output
Set value corresponding to 20mA.
- Alarm Selection
Set value to be output when the gauge misses the echo.
Low(3.9mA), High(22mA) or Hold Last Value