What is the required connected load per charging station?
For the connected load, there is no defined value but it is dependent on the
available connected load. For each charging station, the connected load
may be max. 32 A. The maximum permissible current (10 A, 13 A, 16 A, 20
A, 25 A, 32 A) is configured via the DIP switches in the housing.
What should I do if the power supply terminals cannot be opened?
To open the power supply terminal, a screwdriver with the following proper-
ties is required:
●
Flathead screwdriver
●
Blade length: front of at least 3 cm bare blade (no plastic covering)
●
Blade width: 4 - 5.5 mm (3/16'')
To open the power supply terminal, proceed as follows:
Caution
Risk of breaking the power supply terminal!
Do not press the screwdriver up, down or to the side in the power supply
terminal.
1) Insert the screwdriver into the power supply terminal as shown
Illustration 2-1: Power supply terminal
2) Using moderate force, press the screwdriver straight into the power sup-
ply terminal until the contact opens. The angle of the screwdriver
changes while pressing in.