ERROR_PILOT
Error group:
0x[xxx]4
Unexpected pilot signal received. The charging station has received an un-
expected or undefined signal from the connected vehicle.
Measures
Check cables and connectors for possible damage and replace if necessary.
ERROR_FI
Error group:
0x[xxx]5
The internal fault current monitoring of the charging station was triggered. An
excessively high leakage or fault current has occurred in the charging station
vehicle circuit.
The cause may be a failed self-test of the charging station. The error may
also have been triggered by the connected vehicle.
Error code
Cause
0x8005
Self-test of fault current monitoring failed during restart of the charging
station.
0x8015
Self-test of fault current monitoring failed after an error recovery. Either
communication error with safety logic (error display only in firmware ver-
sion 3.06) or fault current monitoring does not work.
0x8025
Self-test of fault current monitoring during connection of a vehicle failed.
This self-test is indicated by the LED bar glowing orange for 3 seconds
when the vehicle is plugged in.
0x8035
Check of the fault current monitoring status immediately before the con-
tactor was switched on failed.
0x8045
Timeout during attempt to turn on the contactor.
0x8065
Switching on the contactor in the event of an error (tripping by fault cur-
rent within 5 seconds -> soft fault). Charging cable must be disconnected.
0x8075
A fault current limit was exceeded during the charging procedure. The
permissible limits are 6 mA for DC residual currents and 30 mA for AC
residual currents.
Measures
If the error occurs during startup without a connected vehicle: Disconnect the
charging station for a short time (30 seconds) via the line circuit breaker.
If the error occurs when the vehicle is plugged in: Cancel charging and
switch off charging station for a short time (30 seconds) via the line circuit
breaker. Then restart the charging process.