Î
Screw on the filter pot and tighten it us-
ing the filter key.
Î
Restart the raw water flow.
Î
Switch on the unit using the "ON/OFF"
key.
몇
Warning
Danger of damage to the plant. The follow-
ing values should not be exceeded when
you make changes to the plant settings:
–
Pump pressure maximum 1.4 MPa (FW
model), 2.1 MPa (BW variant)
–
Maximum drinking water quantity 600 l/
h
–
The concentrate quantity should not fall
below the value at the time of startup
Note
There is a time delay before the plant reacts
to the changes done to the regulating valve.
Hence do the settings at the pressure regu-
lation valve in small steps and wait for the
respective effect.
(1) Drinking water flow has fallen from
_______ l/h to _______ l/h
1 Concentrate regulation valve
2 Pressure regulation valve
3 Flow meter for drinking water
4 Flow meter for concentrate
Î
Read the quantity of drinking water at
the flow meter for drinking water and
compare it to the value when the plant
was started (see start-up report). If the
drinking water flow ahs fallen to ______
l/h, then do the following fine regulation:
Î
Close the pressure regulation valve in a
clock-wise direction until the flow meter
for the drinking water has almost
achieved the target value.
Î
Close the concentrate regulation valve
slowly in the clock-wise direction until
the required target value is reached for
the two flow meters of the concentrate
and the drinking water.
Note
Inform Kärcher Customer Service if this fine
regulation does not lead to any changes to
the drinking water flow.
(2) Conductivity of drinking water has in-
creased from _____µS/cm to _____µS/cm
Note
Small increases in the conductivity of drink-
ing water does not affect the quality of the
drinking water.
Î
Read the current conductivity value on
the display of the operating panel and
compare it to the value at the time of
start-up (see start-up report). If the
drinking water conductivity has in-
creased to _____µS/cm, then you need
to rinse the membrane of the RO filter
unit:
Î
Reduce the drinking water output by
opening the pressure regulation value
to approx. 200 l/h.
Î
Operate the plant for approx. 1 hour;
then reset the nominal output by closing
the pressure regulating valve.
Î
Check again the conductivity of the
drinking water.
Note
If rinsing the membrane does not result in
lower conductivity values, then inform
Kärcher Customer Service.
(3) Difference between pump and con-
centrate pressure has increased by
more than ___ MPa
1 Manometre for pump pressure
2 Manometer for concentrate pressure
Î
Read the value on the manometer for
the pump pressure and the concentrate
pressure and determine the differential
pressure.
Î
Compare the ascertained differential
value with the value set at the time of
startup (see startup report).
Î
The membrane filter unit must be
blocked if the differential pressure has
increased by more than ______ MPa;
no further adjustments are possible.
Stop production of drinking water and
inform Kärcher Customer Service.
Danger
Risk of burns injury on account of chemi-
cals. Please wear safety gloves and safety
goggles while handling acid-resistant
chemicals.
Note
The values for dosing the different chemi-
cals are based on the raw water analysis
and the plant output. Kärcher Customer
Service will enter the dosing quantities re-
quired for your plant in the following table at
the time of startup.
1 Cover
2 Mixing rod
3 Dosing pump
4 Dosing container
Î
Wear safety gloves and safety goggles.
Î
Remove the can from the dosing sta-
tion.
Danger
Risk of injury on account of chemical reac-
tion. The dosing stations should not get in-
terchanged and be filled up with the wrong
chemicals.
몇
Warning
Risk of flocculation or other undesirable
chemical reactions. Use only drinking water
from WPC 600 BW/FW to mix the chemi-
cals.
The dosing depends on the filling level in
the dosing container.
Fully emptied dosing container.
Î
Fill 10 l drinking water in the dosing con-
tainer.
Î
Using a measuring beaker, measure 7.5
times the quantity mentioned in the dos-
ing table and add it to the dosing con-
tainer.
Î
Fill up the dosing container up to the
mark "75 l" with chlorine-free water.
Fine regulation of the operating pres-
sures
Mixing the chemicals
Dosing table
Dosing
con-
tainer
Chemical
Dosing per 10
l of dosing so-
lution [ml]
Pre-
chlorin-
ation
RM 852 Ster-
ilisation
agent*
Calcium hy-
prochlorite *
Pre-
flock-
ing
RM 5001
Anti-
scalant
RM 5000
Hardness
stabiliser
Post-
chlorin-
ation
RM 852 Ster-
ilisation
agent*
Calcium hy-
prochlorite *
* These chemicals can be used as alter-
natives.
Summary of Contents for WPC 600 BW
Page 2: ......
Page 12: ...12 Deutsch R ckseite Bleibt leer damit das Blatt herausgetrennt werden kann...
Page 22: ...22 English Rear side Is kept blank so that the sheet can be separated...
Page 32: ...32 Fran ais Verso Reste vide afin que la feuille peut tre retirer...
Page 42: ...42 Italiano Tergo Resta vuoto in modo da poter separare il foglio...
Page 52: ...52 Espa ol Parte posterior En blanco para separar la hoja...
Page 60: ...60 WPC B 1 024 dH C S cm h MPa MPa MPa l h S cm ____...
Page 61: ...61 WPC A 1 024 h dH S cm pH pH C MPa MPa MPa MPa MPa MPa MPa MPa l h l h S cm K rcher...
Page 62: ...62...
Page 72: ...72 T rk e Arka sayfa Sayfan n ayr labilmesi i in bo kal r...
Page 81: ...cc 81 WPC A 1 024 dH pH pH C M a M a M a M a M a M a a a Antiscalant rcher...
Page 82: ...82 cc...
Page 83: ...cc 83 WPC B 1 024 dH C a a ____...
Page 93: ...Nederlands 93 Achterkant Blijft leeg zodat de pagina eruit gehaald kan worden...