4.19
P5 Troubleshooting
Digital display output
4.19.1
Description
4.19.2
High temperature difference between water side heat exchanger water inlet and water outlet
temperatures
protection.
Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user interface.
Possible causes
4.19.3
Temperature sensor not connected properly or has malfunctioned.
Water piping contains air.
Insufficient water flow.
Hydronic system main PCB damaged.