M thermal Mono
90
200208
Midea
M
ther
ma
l Mo
no
Se
rvice M
an
ual
Notes:
1. If the fan motor is running and the DC voltage between terminals P and N on inverter module declined, Relay on the main control board of outdoor unit is
open
.
2. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on IPM module (on the reverse side of the inverter module
PCB). Refer to Figure 4-4.2.
Figure 4-4.4: Relay location of main PCB for refrigerant system
Single phase 4/6/8/10kW unit
Single phase 12/14/16kW unit
Relay
L5/L8/L9 troubleshooting
4.20.8
L5/L8/L9
The wire is not connected properly
NO
Ensure wire is connected properly
Yes
Inverter module PCB has malfunctioned
Yes
Replace inverter module PCB
1
No
Replace the compressor
1. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on IPM module (on the
reverse side of the inverter module PCB). Refer to Figure 4-4.2.
Midea CAC Confidential
M thermal Mono
202008
91
4.21
Inverter module Troubleshooting for three-phase models
Digital display output
4.21.1
Description
4.21.2
Inverter module protection or high pressure protection.
Mono stops running.
Specific error code L0, L1, L2, L4, L5, L8 , L9 is displayed on the user interface and the refrigerant system main
PCB.
Possible causes
4.21.3
Inverter module protection.
DC bus low or high voltage protection.
MCE error(DC bus low or high voltage protection or software over current protection)
Zero speed protection.
Excessive compressor frequency variation.
Actual compressor frequency differs from target frequency.
High pressure protection.
Contactor stuck or 908 self checking fail.
Specific error codes for inverter module protection
4.21.4
Table 4-4.4: Specific error codes
Specific error code
Content
L0
Inverter module protection
L1
DC bus low voltage protection
L2
DC bus high voltage protection
L4
MCE error(DC bus low or high voltage protection or software over current protection)
L5
Zero speed protection
L8
Compressor frequency variation greater than 15Hz within one second protection
L9
Actual compressor frequency differs from target frequency by more than 15Hz protection
Midea CAC Confidential
Mono
Summary of Contents for 06RY1
Page 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Page 2: ...Mono...
Page 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Page 113: ...Mono...
Page 114: ...kaisai com...