3. Check the +15V circuit according to corresponding wiring diagram. If IC4/5/6PIN12 on inverter module output voltage is not +15V means the inverter
module is failed. If voltage output of inverter module is +15V means main PCB is failed.
4. Check the bridge rectifier using one of the following two methods (refer to Figure 4-4.11):
Method 1: measure the resistance between any two of the 5 bridge rectifier terminals. If any of the resistances is close to zero, the bridge rectifier
has failed.
Method 2: dial a multimeter to the diode setting:
- Put the red probe on the DC power output negative terminal (terminal 5) and put the black probe onto each of the AC power input terminals
(terminals 1, 2 and 3) in turn. The voltage between terminal 5 and each of terminals 1, 2 and 3 should be around 0.378V. If the voltage is 0, the
bridge rectifier has failed.
- Put the red probe on the DC power output positive terminal (terminal 4), then put black probe onto each of the AC power input terminals
(terminals 1, 2 and 3) in turn. The voltage between terminal 4 and each of terminals 1, 2 and 3 should be infinite. If the voltage is 0, the bridge
rectifier has failed.
Figure 4-4.11: Bridge rectifier
Three phase AC power input
DC power output
Figure 4-4.10: P N +15V te15V
(
IC4/5/6PIN12
);
N-
(
IC/4/5
、
6
)
PIN13
Schematic diagram
N
+15V
Midea CAC Confidential
M thermal Mono
202008
99
L4 troubleshooting(the same as L1/L2)
4.21.8
Situation 1: L4 error appears immediately after the outdoor unit is powered-on
L4
Replace the inverter PCB
Condition 2: L4 error appears after the compressor has been running for a period of time and the compressor speed is
over 60rps
L4
Compressor is over-current
2
Yes
Replace the compressor
No
Replace the inverter PCB
Notes:
1. Re-start the unit, use clip-on ammeter to measure the compressor current, if the current is normal indicates the compressor is failed, if the current is
abnormal indicates the inverter PCB is failed..
L5/L8/L9 troubleshooting
4.21.9
L5/L8/L9
The wire is not connected properly
NO
Ensure wire is connected properly
Yes
Inverter module PCB has malfunctioned
Yes
Replace inverter module PCB
No
Replace the compressor
Midea CAC Confidential
Mono
Summary of Contents for 06RY1
Page 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Page 2: ...Mono...
Page 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Page 113: ...Mono...
Page 114: ...kaisai com...