user interface. Refer to the Mono Engineering Data Book Part 3, 7.4 “DHW MODE SETTING Menu”.
Domestic hot water demand priority can be ended by changing the switch on controller from "on" to "off".
Table 3-6.5: Component control during fast DHW operation
Component
Wiring
diagram label
6kW
8/10/12/14/16kW
Control functions and states
Inverter compressor
COMP
●
●
Controlled according to load requirement
DC fan motor
FAN
●
●
Controlled according to outdoor heat exchanger
pipe temperature
Electronic expansion valve
EXV
●
●
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge superheat
Four-way valve
ST
●
●
On
Tank electric heater
TBH
●
●
On
6.4
Two zones control
1
Two zones control function is used to control temperature of each zone separately, thus different type radiator will operate
at its optimal temperature and water pump cycle time will be reduced to save energy.
In two zones control for cooling mode, when the setting temperature of a certain zones is reached, the zone and water
pump of this zone will turn off.
In two zones control for heating mode, the on/off control of zone and water pump is same with cooling mode, but in
addition, the mixing valve (3-way valve SV3) control function will be activated to adjust the water temperature of the low
temperature zone by control the opening time and closing time of the valve. The mixing valve will only turn on when two
zones control for heating is activated. On other conditions, the mixing valve will keep off.
When the valve initially turns on, the opening time and closing time is same and then the time is controlled according to
the difference between water pipe temperature and setting water temperature of the controlling zone.
Hydraulic adapter PCB (Optional)
With the help of hydraulic adapter PCB, totally 8 thermostats can be used at the same time for maximum 8 rooms to
control heat pump.
Note:
1.
U
nits just have the controlling function, while the mixing valve, water pump of each zone need to be field
supplied and connect to unit.
Midea CAC Confidential
Mono
Summary of Contents for 06RY1
Page 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Page 2: ...Mono...
Page 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Page 113: ...Mono...
Page 114: ...kaisai com...