M thermal Mono
24
202008
Midea
M
ther
ma
l Mo
no
Se
rvice M
an
ual
5.8
Module Temperature Protection Control
This control protects the module from abnormally high temperatures
.
Figure 3-5.3: Module Temperature Protection Control
When the module temperature rises at or above Tf2 the system displays C7 protection and the unit stops running. When
the module temperature drops at or below Tf0-1, the compressor enters re-start control.
6kW
8-10kW
Tf2
75
81
Tf0
69
75
Module temperature
≥
Tf2
Module temperature
≤
Tf0-1°C
Normal operation
Module Temperature Protection, error code C7 is displayed
Midea CAC Confidential
12-16kW 3ph
84
78
Mono
Summary of Contents for 06RY1
Page 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Page 2: ...Mono...
Page 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Page 113: ...Mono...
Page 114: ...kaisai com...