bH Troubleshooting
Digital display output
4.22.1
Description
4.22.2
PED PCB failure
Split stops running.
Error code is displayed on hydronic box main PCB and user
interface.
Possible causes
4.22.3
Power supply problem.
PED board broken.
IPM module broken.
Midea CAC Confidential
M thermal Mono
202008
101
Procedure
4.22.4
bH
Power supply problem. After 5
minutes of power-off interval,
power on again and observe
whether it can be recovered.
Yes
Increase the power voltage to the
required range.
No
PED
1
board broken.
Yes
Replace PED PCB and power on again.
No
IPM module broken.
Yes
Replace IPM module and power on again.
Notes:
1.
PED is port CN22 on the hydronic box main PCB (labeled 11 in Figure 4-
KHC
-12(14,16)RY3
B outdoor unit inverter module ).