Procedure
4.6.4
E5 / E6 / E9 / EA
Temperature sensor connection on
refrigerant system main PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed
2
Yes
Replace the sensor
No
Replace refrigerant system main PCB
Notes:
1.
Air side heat exchanger refrigerant outlet temperature sensor and outdoor ambient temperature sensor connections are port CN9 on
the
KHC
-06(08,10)RY1 outdoor unit refrigerant system main PCB (labeled 12 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN9 on the
KHC
-12(14,16)RY3
outdoor unit refrigerant system main PCB (labeled 17 in Figure 4-2.4 in Part 4, 2.1 “Main PCBs for
Refrigerant System, Inverter Module”). Discharge pipe temperature sensor connection are port CN8 on the
KHC
-06(08,10)RY1
outdoor unit
refrigerant system main PCB (labeled 15 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN4 on the
KHC
-12(14,16)RY3
outdoor unit refrigerant system main PCB (labeled 15 in Figure 4-2.4 in Part 4, 2.1 “Main PCBs for Refrigerant System,
Inverter Module”). Suction pipe temperature sensor connection are port CN1 on the
KHC
-06(08,10)RY1
outdoor unit refrigerant system main
PCB (labeled 14 in Figure 4-2.2 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter
Module”), port CN8 on the
KHC
-12(14,16)RY3
outdoor unit
refrigerant system main PCB (labeled 16 in Figure 4-2.4 in Part 4, 2.1 “Main PCBs for Refrigerant System, Inverter Module”).
2.
Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s
resistance
characteristics table, the sensor has failed. Refer to Table 4-5.1, and Table 4-5.2 in Part 4, 5.1 “Temperature Sensor Resistance Characteristics”
Midea CAC Confidential
M thermal Mono
202008
63
4.7
EE Troubleshooting
Digital display output
4.7.1
Description
4.7.2
Hydronic system EEPROM error.
Mono stops running.
Error code is displayed on hydronic system main control board for refrigerant system and user
interface.
Possible causes
4.7.3
Hydronic system main PCB EEPROM is not connected properly.
Hydronic system main PCB damaged.
Procedure
4.7.4
EE
Hydronic system EEPROM
1
is not
connected properly
Yes
Ensure the EEPROM is connected
properly
No
Replace hydronic system main PCB
Notes:
1. Hydronic system main PCB EEPROM is designated IC18 on the hydronic system main PCB (labeled 29 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic
System”).
Midea CAC Confidential
Mono
Summary of Contents for 06RY1
Page 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Page 2: ...Mono...
Page 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Page 113: ...Mono...
Page 114: ...kaisai com...