Pb Troubleshooting
Digital display output
4.23.1
Description
4.23.2
Water side heat exchanger anti-freeze protection.
Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and
ANTI.FREEZE
icon
is
displayed on user interface.
Possible causes
4.23.3
Normal system protection.
Temperature sensor not connected properly or has malfunctioned.
Hydronic system main PCB damaged.
Procedure
4.23.4
Pb
Outdoor ambient temperature is lower
than 4°C
Yes
Normal system protection. The system
will resume automatically
1
No
Water side heat exchanger water outlet
temperature sensor, water inlet
temperature sensor or backup electric
heater outlet water temperature sensor
loose
2
Yes
Ensure the temperature sensor is
connected properly
No
Water side heat exchanger water outlet
temperature sensor, water inlet
temperature sensor or backup electric
heater outlet water temperature sensor
has short-circuited or failed
3
Yes
Replace the temperature sensor
No
Replace outdoor main PCB
Notes:
1. Refer to Part 3, 5.7 “Water Side Heat Exchanger Anti-freeze Protection Control”.
2. Backup electric heater water outlet temperature sensor,
water side heat exchanger water inlet temperature sensor and water side heat exchanger water
outlet temperature sensor connections are port CN6 on the hydronic system main PCB (labeled 8 in Figure 4-2.1 in Part 4, 2.2 “Main PCB for Hydronic
System”).
3. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor’s resistance
characteristics table, the sensor has failed. Refer to Part 2, 1 “Layout of Functional Components” and to Table 4-5.3 in Part 4, 5.1 “Temperature Sensor
Resistance Characteristics”.
Midea CAC Confidential
M thermal Mono
202008
103
4.24
Pd Troubleshooting
Digital display output
4.24.1
Description
4.24.2
High temperature protection of air side heat exchanger refrigerant outlet in cooling mode. When the air side
heat
exchanger refrigerant outlet temperature is higher than 61°C for more than 3 seconds, the system
displays Pd
protection and Mono stops running. When the air side heat exchanger refrigerant outlet
temperature
returns drops below 55°C , Pd is removed and normal operation resumes.
Mono stops running.
Error code is displayed on refrigerant system main control board for refrigerant system and user interface.
Possible causes
4.24.3
Temperature sensor not connected properly or has malfunctioned.
Poor condenser heat exchange.
Fan motor damaged.
Hydronic system main PCB damaged.
Midea CAC Confidential
Mono
Summary of Contents for 06RY1
Page 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Page 2: ...Mono...
Page 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Page 113: ...Mono...
Page 114: ...kaisai com...