Procedure
4.17.4
P3
The power supply is abnormal
Yes
Check the power supply equipment
No
The condenser heat exchange is poor
1
Yes
Inspect the system and fix the error
No
The high pressure side is blocked, caused
by crushed or bent pipe or blocked EXV
2
Yes
Inspect the system and fix the error
No
Inverter module has short-circuited
3
Yes
Replace the inverter module
No
Compressor has malfunctioned
4
Yes
Replace the compressor
No
Replace outdoor main PCB
Notes:
1. In heating mode check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt/blockages. In cooling mode check air side
heat exchanger, fan(s) and air outlets for dirt/blockages.
2. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to
be lower than normal.
3. Set a multi-meter to buzzer mode and test any two terminals of P N and U V W of the inverter module. If the buzzer sounds, the inverter module has
short-circuited.
4. The normal resistances of the inverter compressor are 0.7-
1.5Ω
among U V W and infinite between each of U V W and ground. If any of the resistances
differ from these specifications, the compressor has malfunctioned.
Midea CAC Confidential
Mono
Summary of Contents for 06RY1
Page 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Page 2: ...Mono...
Page 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Page 113: ...Mono...
Page 114: ...kaisai com...