Situation 2: L0 error appears immediately after the compressor starts up
L0
DC bus wire is not connected properly
1
Yes
Ensure DC bus wire is connected properly
No
Compressor has malfunctioned
2
Yes
Replace the compressor
No
Replace the main PCB
Notes:
1. The DC bus wire should run from the N terminal on the inverter module, through the current sensor (in the direction indicated by the arrow on the current
sensor), and end at the N terminal of capacitor. Refer to Figure 4-4.7.
Figure 4-4.7: DC bus wire connection
(
L1L2L3,PIN- POUT
)
L1
,
L2
,
L3
Pin
,
Pout
2. The normal resistances of the inverter compressor are 0.7-
1.5Ω among U V W and infinite between each of U V W and ground. If any of the
resistances
differ from these specifications, the compressor has malfunctioned.