5.3
Discharge Temperature Protection Control
This control protects the compressor from abnormally high temperatures and transient spikes in temperature.
Figure 3-5.3: High discharge temperature protection control
When the discharge temperature rises above 115°C the system displays P4 protection and the unit stops running. When
the discharge temperature drops below 95°C, the compressor enters re-start control.
Figure 3-5.4:Low discharge temperature protection control
When the discharge temperature is lower than suction temperature for more than 5 minutes, the system displays EA
protection and the unit stops running. When the discharge temperature is higher than suction temperature, the
compressor enters re-start control.
5.4
Compressor Current Protection Control
This control protects the compressor from abnormally high currents.
Figure 3-5.5: Compressor current protection control
Table 3-5.1: Current limitation for compressors
Model name
6kw
8-10kw 12-16kw 1ph 12-16kw 3ph
Current
max
18A
19A
30A
14A
When the compressor current rises above Current
max
the system displays P3 protection and the unit stops running. When
the compressor current drops below Current
max
, the compressor enters re-start control.
Discharge temperature > 115°C
Discharge temperature < 95°C
Normal operation
High discharge temperature protection, error code P4 is displayed
Tp
<
Th for more than 5 minutes
Tp
≥
Th
Normal operation
Low discharge temperature protection, error code EA is displayed
Current > Current
max
Current < Current
max
Normal operation
Compressor current protection, error code P3 is displayed
Midea CAC Confidential
M thermal Mono
202008
23
Part
3
- Con
trol
5.5
Voltage Protection Control
This control protects the Mono from abnormally high or abnormally low voltages.
Figure 3-5.4: Compressor voltage protection control
When the phase voltage of AC power supply is at or above 265V for more than 30 seconds, the system displays H7
protection and the unit stops running. When the phase voltage drops below 265V for more than 30 seconds, the
refrigerant system restarts once the compressor re-start delay has elapsed. When the phase voltage is at or below 172V,
the system displays H7 protection and the unit stops running. When the AC voltage rises to at or more than 187V, the
refrigerant system restarts once the compressor re-start delay has elapsed.
5.6
DC Fan Motor Protection Control
This control protects the DC fan motors from strong winds and abnormal power supply. DC fan motor protection occurs
when any one of the following three sets of conditions are met:
Outdoor ambient temperature is at or above 4°C and actual fan speed differs from target fan speed by more than
200rpm for more than 3 minutes.
Outdoor ambient temperature is below 4°C and actual fan speed differs from target fan speed by more than 300rpm
for more than 3 minutes.
Actual fan speed is less than 150rpm for more than 90 seconds.
When DC fan motor protection control occurs the system displays the H6 error code and the unit stops running. After 3
minutes, the unit restarts automatically. When H6 protection occurs 10 times in 120 minutes, the HH error is displayed.
When an HH error occurs, a manual system restart is required before the system can resume operation.
5.7
Water Side Heat Exchanger Anti-freeze Protection Control
This control protects the water side heat exchanger from ice formation. The water side heat exchanger electric heater is
controlled according to outdoor ambient temperature, water side heat exchanger water inlet temperature and water side
heat exchanger water outlet temperature.
In heating mode, if the outdoor temperature falls below 3°C and either the water side heat exchanger water inlet
temperature or water side heat exchanger water outlet temperature are below 25°C, the water side heat exchanger
electric heater turns on. When the outdoor ambient temperature rises above 5°C and either the water side heat exchanger
water inlet temperature or water side heat exchanger water outlet temperature are above 30°C, the water side heat
exchanger turns off.
When water side heat exchanger anti-freeze protection occurs the system displays error code Pb and the unit stops
running.
Voltage
≥
265V
or Voltage
≤
172V
254V < Voltage < 187V
Normal operation
Compressor voltage protection, error code H7 is
displayed
Midea CAC Confidential
Mono
Summary of Contents for 06RY1
Page 1: ...SERVICEMANUAL MONO TYPE HEAT PUMP R32...
Page 2: ...Mono...
Page 4: ...M thermal Mono 2 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 16: ...M thermal Mono 14 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 32: ...M thermal Mono 30 202008 Midea M thermal Mono Service Manual Midea CAC Confidential Mono...
Page 51: ...M thermal Mono 202008 51 Midea CAC Confidential Mono...
Page 113: ...Mono...
Page 114: ...kaisai com...