Powador-protect
Auto | On | Off
NOTE: Configures the support for grid shutdown by a Powador-protect
connected to the digital input of the device.
↻
Auto/On: A Powador-protect is operating in the photovoltaic sys-
tem and is connected to the device at the digital input/output.
F
Set the operating mode for Powador-protect.
Auto: The device automatically detects a Powador-protect integrated
into the photovoltaic system.
On: The digital signal of the Powador-protect must be present at the di-
gital input of the device for the device to begin feed-in.
Off: The device does not check whether a Powador-protect is integrated
into the PV system.
4
1
2
3
4
Iso.resistor
F
Set threshold value (in 1kOhm increments) at which the insulation
monitor reports a fault.
4
1
2
3
4
Power reduction P(f)
NOTE: The unit supports the internal power factor correction after
P(f).
1 Open the menu: Press the
Right arrow button
or
Enter
button
.
Note: All the parameters are configurable here and via the WEB in-
terface
Configuration via web user interface [See sec-
4
1
2
3
4
Fault ride-through
NOTE: The device supports dynamic grid stabilization (Fault Ride-
Through).
F
Further parameterisation is possible via the web interface
4
1
2
3
4
Reactive power
1 Open the menu: Press the
Right arrow button
or
Enter
button
.
2 Activating reactive power process: Select process a press the
Enter button
. The active process is highlighted.
4
1
2
3
4
cos-phi const.
1- 0.3
More detailed information about the procedure can be found at:
1 Reactive power control [See section 10.1
2 Determine the specified displacement factor.
Over-excited | un-
der-excited
F
If a power factor not equal to 1 is selected: Select the type of phase
shift: under-excited (inductive load), over-excited (capacitive load).
4
1
2
3
4
Q constant
0 – 100%
More detailed information about the procedure can be found at:React-
ive power control [See section 10.1
F
Set the idle power Q (in %) to a fixed value.
Under-excited |
over-excited
F
Select the type of phase shift.
NOTE: Under-excited relates to inductive load, over-excited relates to
capacitive load.
4
1
2
3
4
cos-phi(P/Plim)
NOTE: More detailed information about the procedure can be found
at:
Reactive power control [See section 10.1
F
Open the menu: Press the
Right arrow button
or
Enter
button
.
4
1
2
3
4
Settling time
1s – 120 s
F
Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient re-
sponse corresponds to a first-order filter (PT-1) with settling time =
5Tau.