8
Commissioning
8.1
Requirements
DANGER
Lethal voltages are still present in the connections and cables of the device even after the device has
been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
›
The device is only permitted to be commissioned by a qualified professional.
›
Unauthorised persons must be kept away from the device.
WARNING
Risk of burns from hot surface.
Heat sinks become very hot when in operation.
›
Never touch the heat sinks after commissioning the device.
›
Allow the heat sinks at least 10 minutes to cool down before cleaning.
↻
The device has been mounted and electrically installed.
↻
The battery supplies a voltage above the configured start voltage.
1 Connect the grid voltage using the external circuit breakers.
2 Activate the battery and connect via the external DC isolator switch.
»
During initial start-up: Follow the instructions of the New Connection Wizard.
»
Following an interruption in operation Device waits for the prompt of the EMS/PMS
KACO blueplanet gridsave 50.0TL3-S
Page 29