Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Change password for
"user"
Password of the
logged-on user | New
password for the
"user" access | Confirm
new password
1 Enter old password.
2 Enter a new, secure password.
3 Confirm and apply new password.
4
1
2
3
4
Modbus
NOTE: Option to set the Modbus port.
4
1
2
3
4
Power Limitation
NOTE: The output power of the device can be set permanently to a
lower value than the maximum output power by the internal power
limitation. This may be necessary in order to limit the maximum
power rating of the system at the grid connection point, upon the grid
operator's request.
4
1
2
3
4
Internal
NOTE: Opportunity to limit the power internally
Power Limitation
Status
F
Specify the activation status.
4
1
2
3
4
Maximum apparent
power Slim
1000 – S
max
[VA]
NOTE: The max. apparent power limits the internal power of the
device.
More detailed information at:
Other grid-supporting functions that are effective in the case of active
power [See section 10.4
F
Enter the value or set the value using the slider.
The apparent power is limited globally to the configured value in VA. All
active and reactive power control values use S
lim
instead of S
max
as
100 %, if S
lim
is configured.
4
1
2
3
4
Maximum active power
Plim
1.0 - 100.0 [% Slim]
Password protection
Status
More detailed information at:
Other grid-supporting functions that are effective in the case of active
power [See section 10.4
F
Enter the value or set the value using the slider.
Active power is limited globally to the configured value in % S
lim
or S
max
.
1 Optional: Activate password protection.
2 Confirm the action field.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Settling time
200 – 30000 [ms]
Password protection
Status
1 Specify the settling time.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Settling time
200 - 60000 [ms]
1000
Password protection
Status
1 Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient
behaviour corresponds to a first-order filter (PT-1) with transient
time = 5Tau.
2 Activate optional password protection.
3 Confirm the action field.
KACO blueplanet gridsave 50.0TL3-S
Page 44