Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Gradient with overfre-
quency – charging
0 – 200 (%/Hz) ;
40 (%/Hz)
Gradient with under-
frequency – charging
0 – 200 (%/Hz) ;
40 (%/Hz)
1 Specify gradient for charging with overfrequency.
2 Specify gradient for charging with underfrequency.
4
1
2
3
4
Frequency of the max-
imum deactivation
threshold
45 -50.2 (Hz)
Frequency of the min-
imum deactivation
threshold
45 -50.2 (Hz)
1 Set frequency of the maximum deactivation threshold.
2 Set frequency of the minimum deactivation threshold.
Not for IL,
IT
4
1
2
3
4
P(f) deactivation time
0 – 3600 [s]
F
Specify time for power reduction (if mode 1 is active).
4
1
2
3
4
P(f) deactivation gradi-
ent
0 – 60000 [% / min]
F
Determine the deactivation gradient.
4
1
2
3
4
Dynamic gradient
mode
On | Off
F
Activate dynamic gradient.
4
1
2
3
4
Maximum dynamic
gradient frequency
50.22 – 70.5 [Hz]
Minimum dynamic
gradient frequency
45 – 50 [Hz]
F
Specify dynamic gradient frequency in Hz.
4
1
2
3
4
P(f) settling time
200 – 2000 [ms]
Password protection
Status
1 Set the P(f) settling time mode.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Output gradient limita-
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
F
Specify the increasing and decreasing output gradient.
4
1
2
3
4
Power reduction P(U)
NOTE: To prevent the device from shutting down due to overvoltage
protection, the active power can be regulated in addition to reactive
power control in order to reduce the active power feed-in whereby
the output voltage is reduced.
4
1
2
3
4
Reference power
Actual power |
Nominal power
F
Select the power-dependent control method.
KACO blueplanet gridsave 50.0TL3-S
Page 46
EN