Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Settling time
200 - 60000 [ms]
1000
Password protection
Status
1 Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient
behaviour corresponds to a first-order filter (PT-1) with transient
time = 5Tau.
2 Activate optional password protection.
3 Confirm the action field.
4
1
2
3
4
Priority mode
Q-Priority | P-Prior-
ity
F
Set priority for reactive power – Q or active power – P.
NOTE: When it comes to P priority, the reactive power adjustment
range is limited subject to the active power that is currently available
and fed in.
4
1
2
3
4
Node 1- Node 10
Power / Excitation /
Voltage
0 – 100 [%]
F
Set the reactive power of the node as a percentage of the maximum
power.
Over-excited | un-
der-excited
F
Select the type of phase shift.
NOTE: Over-excited relates to a capacitive load, under-excited relates
to an inductive load.
0 – 100 [% Unom]
F
Enter the voltage of the node in volts.
NOTE: The voltage values of the nodes must increase continuously. At
voltages below the 1st node and voltages above the last node, the re-
active power value of the 1st or last node is used each time.
Not for IL,
IT
4
1
2
3
4
P(f) operation mode
Off | Mode 1 |
Mode 2
F
Specify the operation mode.
4
1
2
3
4
Power reference mode
with overfrequency
Actual power |
Nominal power
Power reference mode
with underfrequency
Actual power |
Nominal power
1 Specify control method with overfrequency.
2 Specify control method with underfrequency.
4
1
2
3
4
Activation threshold
with overfrequency
50.2 – 70 (Hz)
Activation threshold
with underfrequency
40 – 45 (Hz)
1 Set frequency thresholds for activating the power limitation with
overvoltage.
2 Set the frequency thresholds for activating the power limitation
with undervoltage.
4
1
2
3
4
Gradient with overfre-
quency – feed-in
0 – 200 (%/Hz) 40
(%/Hz)
Gradient with under-
frequency – feed-in
0 – 200 (%/Hz) 40
(%/Hz)
1 Specify gradient for feed-in with overfrequency.
2 Specify gradient for feed-in with underfrequency.
KACO blueplanet gridsave 50.0TL3-S
Page 45
EN