the configured shutdown time, the device shuts down. In case of an island, this will shut down the island instantaneously.
If the grid stabilizes, what might be the case if the ROCOF event was due to a short disturbance in the power grid, the in-
verter will resume normal operation. In the event of active stage 1, the device switches to zero current mode, and re-
starts the infeed after a few 100ms. At stage 2, the device has shut down and the set reconnection conditions apply.