DC-side
blueplanet gs 50.0TL3-S B1 WM OD IIGB
blueplanet gs 50.0TL3-S B1 WM OD IIGM
blueplanet gs 50.0TL3-S B1 WM OD IIGL
blueplanet gs 50.0TL3-S B1 WM OD IIGX
Cable diameter for cable fitting
15 - 21 mm
Fitting for DC connection
M32
Tightening torque
6 - 12
Tab. 2:
Requirement for supply lines and DC fuses
AC-side
blueplanet gs 50.0TL3-S B1 WM OD IIGB
blueplanet gs 50.0TL3-S B1 WM OD IIGM
blueplanet gs 50.0TL3-S B1 WM OD IIGL
blueplanet gs 50.0TL3-S B1 WM OD IIGX
Max. conductor cross-section
95 mm²
Min. cable cross-section
35mm²
3
Length of insulation to be stripped off
25 mm
Tightening torque
10 Nm
Connection type
Screw terminal/PE bolt
Ground conductor connection
M8
Fuse protection for installation provided by customer
min. 100 A / max.125 A
Fitting for AC connection
M63
Cable diameter for cable fitting
32 - 42 mm
Tab. 3:
Requirement for supply lines and AC fuses
Interfaces
blueplanet gs 50.0TL3-S B1 WM OD IIGB
blueplanet gs 50.0TL3-S B1 WM OD IIGM
blueplanet gs 50.0TL3-S B1 WM OD IIGL
blueplanet gs 50.0TL3-S B1 WM OD IIGX
Cable diameter for cable fitting
11 - 17 (M25) 5 - 9.5 (M16) mm
Ethernet connection type
RJ45
Ethernet cable cross-section
0.25 - 0.5 mm²
Tab. 4:
Requirement for supply lines and DC fuses - interfaces
3
The loop impedance at any point between the installation field and the battery must be Zs <Un / Ia (Un: nominal AC
voltage, Ia: current for triggering device protection within 200 ms).
KACO blueplanet gridsave 50.0TL3-S
Page 21