Blueplanet 50.0TL3 B1 WM OD IIGB
↻
Connection cable with 2 x 1 strands already on the device.
1 Unscrew the cable fitting [ W_ws 36].
2 Remove the outer cladding of the DC cables.
3 Pass the DC cables through the cable fittings into the connection compartment.
4 Fit DC lines with an M8 ring cable lug [max. width b 20 mm].
5 Close the accidental contact cover on the DC- / DC+ connection.
6 Screw the negative (-) cable end onto the DC connection according to the polar-
ity of the battery [ W13 / 6 -12 Nm].
7 Screw the positive (+) cable end onto the DC connection according to the polar-
ity of the battery [ W13 / 6 - 12 Nm].
8 Check secure fit of all connected cables.
9 Close the contact protection cover on the DC- / DC+ connection.
10 Make sure that the polarity is correct, and that the inrush current is ensured at
max. 100A.
11 Fit the protective cover and secure using the 4 screws [ T15 / 2.3 Nm].
12 Tighten the cable fittings [ W_ws 36 / 5 Nm].
M8
M8
20 mm
DC+ DC-
Fig. 21:
DC connection B version
7.6
Creating equipotential bonding
↻
The device has been installed on the mount.
1 Strip the insulation from the equipotential bonding cable.
2 Check that the connected cable is fitted securely.
»
The housing is included in the equipotential bonding.
1
Fig. 22:
Additional grounding point
1 Earthing bolt
7.7
Connecting the interfaces
7.7.1
Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injury or death may result from improper use of the interface connections and failure to observe
protection class III.
›
The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with pro-
tection class III.
CAUTION
Damage to the device from electrostatic discharge
Components inside the device can be damaged beyond repair by static discharge.
›
Note the ESD protective measures.
›
Earth yourself before touching a component by touching a grounded object.
KACO blueplanet gridsave 50.0TL3-S
Page 25
EN