Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Remote config
On / Off
F
If necessary, activate the remote configuration.
4
1
2
3
4
Remote update
On / Off
F
If necessary, activate the remote update.
4
1
2
3
4
Portal Connection test
Off | Meteocontrol |
User-defined 1-4:
↻
Your IT infrastructure must be adequately protected.
F
Select operating mode.
Off: The connection to the portal is deactivated.
Meteocontrol: The device attempts to connect to the Webportal blue-
planet web of meteocontrol.
User defined 1-4: The device attempts to log on via a user-defined
portal that was set up by way of remote access.
4
1
2
3
4
Modbus TCP
F
Activate/disable function.
4
1
2
3
4
Activation
NOTE: The menu options "Write access" and "Port" are only dis-
played with TCP activated.
1 Activate Modbus TCP.
4
1
2
3
4
Write access
F
Allow Modbus TCP write access.
4
1
2
3
4
Port
F
Set network port.
4
1
2
3
4
Connection status
Indicates the status of the network connection.
4
1
2
3
4
Parameters
F
Press the
Right arrow button
or
Enter button
.
NOTE: The device does not display the "Parameters" menu in the
standard configuration. To display the Parameters menu:
1 Open the menu.
2 Simultaneously hold down the
Up
and
Down buttons
for sev-
eral seconds.
4
1
2
3
4
Country
NOTE: This option influences the country-specific operating settings of
the device. Please consult the service department of the system manu-
facturer for further information.
1 Enter the four-digit password using the 4-way button. The password
is device-specific.
2 Confirm the entry with the
Enter
button.
3 Set the desired country setting.
CH, DE, ES,
FR, GB, GR,
IT, JO, JP,
LU, TH, ZA
4
1
2
3
4
Grid type/guideline
F
Select the grid type for the device’s installation location.
UD
4
1
2
3
4
Nominal grid voltage
F
Set the specified grid voltage for the site where the unit is used
(please contact the service department of the system manufacturer).
4
1
2
3
4
Grid parameter
F
Open the menu: Press the
Right arrow button
or
Enter
button
.
AT, BG, CZ,
FR-OLD,
FR-VFR13,
FR-VFR14,
IE, JP, NL,
PL, PT, TR,
TW, UD
4
1
2
3
4
Overvoltage shutd. Av-
erage value over ten
minutes
1 Specify the shutdown threshold for overvoltage shutdown.
ð
The 10-minute average for the measured voltage as per
EN50160 is used.
2 Set period from occurrence of the fault to shutdown of the device.
KACO blueplanet gridsave 50.0TL3-S
Page 35