Country-
spec. Set-
tings
Men
u
level
Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Precharge Unit
Displays the total battery voltage
Displays the DC voltage connected to the device
Temperature of the unit
Status of the unit
Error status of the unit
4
1
2
3
4
Vendor
The display shows information about the device manufacturer.
9.3.2
Configuration via web user interface
NOTE
In addition to the parameters in the chapterMenu [See section 9.3.1
Page 32], additional parameters are
available and accessible via the web user interface. To do so, enable
Remote config
in
Network
un-
der
Webserver
and enter the device IP address into your browser.
Country-
spec. Set-
tings
Level Display/
Setting
Action in this menu/meaning
4
1
2
3
4
Operating settings
NOTE: Options for advanced setting of the operating parameters.
4
1
2
3
4
Minimum battery
voltage
500 – 700 [V]
NOTE: The minimum battery voltage is specified automatically in ac-
cordance with the country-specific GridCode.
F
Apply the settings in accordance with the specifications of the sys-
tem integrator.
4
1
2
3
4
Iso.resistor
F
Set threshold value (in 1kOhm increments) at which the insulation
monitor reports a fault.
4
1
2
3
4
EMS communication
timeout
NOTE: The menu item is only available in the EMS in the battery.
4
1
2
3
4
Operation mode
ON | OFF
F
Switch on the function for monitoring the system.
4
1
2
3
4
Time
30 s 1 – 600 [s]
F
Specify the interruption period by which time the signal must ap-
pear.
4
1
2
3
4
FRT (Fault Ride
Through)
NOTE: The device supports dynamic grid stabilization (Fault Ride-
Through).
4
1
2
3
4
Operation mode –
On | Off
F
Select a control process.
On: Activates dynamic grid support using dynamic reactive current.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
Setting | Manual |Pre-
defined zero current
F
Select a control process.
Priority – Reactive cur-
rent limitation | Active
current priority
F
Select a control process.
KACO blueplanet gridsave 50.0TL3-S
Page 41