Figure 51: Airflow Through Chassis
g007408
Lower fan trays
Upper Fan trays
Power
supply
cooling
Card cage
Airflow
divider
Card cage
RELATED DOCUMENTATION
Clearance Requirements for Airflow and Hardware Maintenance for the MX2010 Router | 147
MX2010 Cabinet Size and Clearance Requirements | 128
MX2010 Rack Requirements | 135
MX2010 Rack-Mounting Hardware | 43
MX2010 Cabinet Size and Clearance Requirements
The minimum size cabinet that can accommodate the router is 23.62 in. (60 cm) wide, and 39.37 in. (100 cm)
deep. A cabinet larger than the minimum requirement provides better airflow and reduces the chance of
overheating. To accommodate a single router, the cabinet must be at least 34 U high with a clearance of
36.20 in. (91.95 cm) to accommodate a standard cable manager. It must be at least 40.15 in. (102 cm) to
accommodate an extended cable manager.
128
Summary of Contents for MX2010
Page 1: ...MX2010 Universal Routing Platform Hardware Guide Published 2019 12 03...
Page 28: ......
Page 30: ...MX2010 Power System Description 95 MX2010 Cooling System Description 45 4...
Page 144: ...MX2010 DC Power 48 V System Electrical Specifications 201 122...
Page 146: ......
Page 233: ......
Page 273: ...Figure 98 Loading the MX2010 Router into the Rack g007436 256...
Page 294: ...Figure 113 Reinstalling an AC Power Distribution Module g007440 D 277...
Page 295: ...Figure 114 Reinstalling a DC Power Distribution Module 48 V D g007432 278...
Page 373: ...4 PART Installing and Replacing Components Installing Components 359 Replacing Components 429...
Page 374: ......
Page 620: ......
Page 715: ...6 PART Troubleshooting Hardware Troubleshooting Components 703...
Page 716: ......
Page 744: ......
Page 772: ......
Page 775: ...763...
Page 783: ...772...
Page 796: ...Jewelry Removal Warning 787...
Page 799: ...Operating Temperature Warning 790...
Page 808: ...DC Power Disconnection Warning 799...
Page 812: ...DC Power Wiring Sequence Warning 803...