RELATED DOCUMENTATION
MX2010 Chassis Moving Guidelines | 129
MX2010 Chassis Description | 7
MX2010 Rack Requirements
IN THIS SECTION
Spacing of Mounting Bracket and Flange Holes | 137
Connection to the Building Structure | 138
Rack Size and Strength
The MX2010 router is designed for installation in a rack that complies with either of the following standards:
•
A 19-in. rack as defined in Cabinets, Racks, Panels, and Associated Equipment (document number EIA-310-D)
published by the Electronics Components Industry Association (
).
•
A 600-mm rack as defined in the four-part Equipment Engineering (EE); European telecommunications
standard for equipment practice (document numbers ETS 300 119-1 through 119-4) published by the
European Telecommunications Standards Institute (ETSI). The horizontal spacing between the rails in a
rack that complies with this standard is usually wider than the mounting brackets, which measure
19.2 in. (48.8 cm) from the outer edge to outer edge. Use approved wing devices to narrow the opening
between the rails as required.
•
A 23-in. rack using appropriate 23-in. to 19-in. rack adapters and an appropriate installation shelf that
supports the chassis at the correct vertical position to properly line up the rack mount holes. Juniper
Networks does not supply this hardware, but consideration for the size and weight of the chassis is
important for a safe installation.
The rack rails must be spaced widely enough to accommodate the chassis’s external dimensions:
59.50 in. (151.1 cm) high, 36.20 in. (91.95 cm) deep, and 19 in. (48.3 cm) wide. The outer edges of the
front-mounting flanges extend the width to 19.2 in. (48.8 cm), The spacing of rails and adjacent racks must
also allow for the clearances around the chassis and rack that are specified in
for Airflow and Hardware Maintenance for the MX2010 Router” on page 147
. The cable manager and EMI
135
Summary of Contents for MX2010
Page 1: ...MX2010 Universal Routing Platform Hardware Guide Published 2019 12 03...
Page 28: ......
Page 30: ...MX2010 Power System Description 95 MX2010 Cooling System Description 45 4...
Page 144: ...MX2010 DC Power 48 V System Electrical Specifications 201 122...
Page 146: ......
Page 233: ......
Page 273: ...Figure 98 Loading the MX2010 Router into the Rack g007436 256...
Page 294: ...Figure 113 Reinstalling an AC Power Distribution Module g007440 D 277...
Page 295: ...Figure 114 Reinstalling a DC Power Distribution Module 48 V D g007432 278...
Page 373: ...4 PART Installing and Replacing Components Installing Components 359 Replacing Components 429...
Page 374: ......
Page 620: ......
Page 715: ...6 PART Troubleshooting Hardware Troubleshooting Components 703...
Page 716: ......
Page 744: ......
Page 772: ......
Page 775: ...763...
Page 783: ...772...
Page 796: ...Jewelry Removal Warning 787...
Page 799: ...Operating Temperature Warning 790...
Page 808: ...DC Power Disconnection Warning 799...
Page 812: ...DC Power Wiring Sequence Warning 803...