5 Installation
22
5.6
Pin configuration
Connection
Terminal
Row
Voltage supply for transmitter/controller
Voltage supply (23):
AC 110 to 240 V; -15/+10 %; 48 to 63 Hz
Voltage supply (25):
AC/DC 20 to 30 V; 48 to 63 Hz
Voltage supply (30):
DC 12 to 24 V; +/-15 % (connection only admissible
to
SELV/PELV circuits)
1 N (L-)
2 L1 (L+)
1
NC
3
Voltage supply for proximity switch
DC 12 V (10 to 20 V)
11 +
12 -
1
Voltage supply 24 V for digital sensors type 20263x or type 202614
(connection see chapter "Electrical connection of sensor type 202630 with digital
interface and flow monitor", page 54)
DC 24 V (20.4 to 28.8 V)
14 +
15 -
1
Voltage supply of 5 V for digital sensors type 202613/... and type 202670/...
(connection see chapter "Electrical connection of sensor type 202613", page 44 and see chap-
ter "Electrical connection of sensor type 202670", page 59)
DC 5 V (5.1 to 5.25 V)
1 -
2 +
2
Inputs
NC
5
6
2
Modbus RS485 interface
3 data -
4 data +
7 shielding
RTD temperature probe in 2-wire circuit
8
9
10
ϑ
9
8
10
Summary of Contents for AQUIS 500 RS