Condenser liquid flow is established
•
No uncleared faults or start inhibits exist
Chiller operation
Upon start request, the following occur in sequence:
1. Chiller's system pump run contacts close
2. Variable speed drive pre-charges (approximately 12 seconds)
3. Variable speed drive pre-regulates (approximately 3 seconds)
4. Motor runs
The chiller varies capacity to maintain the leaving chilled liquid temperature setpoint by a specific
sequencing of optional hot gas bypass, variable geometry diffuser, and compressor speed.
Throughout capacity control, the compressor speed is maintained above the minimum required
for the prevailing head condition, to avoid surge. Otherwise, the device maintaining capacity is
controlled by a proportional-integral-derivative control based on leaving chiller liquid temperature.
Pressure and motor current overrides also apply as necessary to maintain operating limits.
The Input Current limit threshold value is determined from several settings, depending on the
chiller control source selected according to the following table.
Table 4: Input current limit threshold
Control source
Active input current limit threshold
Local
Lowest of:
• Local Input Current Limit setpoint (% Input Job FLA)
• Pulldown Input Current Limit (when active)
ISN
Remote Input Current Limit setpoint (comms)
Analog remote
Lowest of:
• Local Input Current Limit setpoint (% Input Job FLA)
• Analog Remote Input Current Limit setpoint
• Pulldown Input Current Limit (when active)
Digital remote
Lowest of:
• Local Input Current Limit setpoint (% Input Job FLA)
• Digital Remote Input Current Limit setpoint
• Pulldown Input Current Limit (when active)
Chilled liquid control settings
The following section contains information on the temperature control setpoint, automatic
temperature shutdown, and automatic temperature restart.
Temperature control setpoint
The temperature at which the chiller controls the chilled fluid leaving the evaporator must be
set by the Operator. The way it is selected depends if the Operator wants this value set locally or
modulated by a remote input.
23
YVAM Control Center
Summary of Contents for YORK YVAM 0350
Page 2: ...2 YVAM Control Center...
Page 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Page 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Page 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Page 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Page 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Page 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Page 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Page 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Page 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...