of subfreezing ambient temperatures, then one of the following freeze protection protocols must
be followed:
•
An appropriate freeze protection fluid selected for the lowest possible ambient temperatures
must be used in the chilled fluid circuit.
-OR-
•
The fluid in the evaporator must be drained as follows:
a. Remove power to the waterbox heaters.
b. Close the chilled fluid circuit isolation valves.
c. Drain the evaporator.
d. Leave the evaporator drain valves open.
In applications where a freeze protection fluid is not used but continuous power to the chiller
control panel, chilled fluid circuit pumps, and evaporator heaters can be guaranteed during periods
of subfreezing ambient temperatures, then one of the freeze damage protection protocols in the
following table must be followed.
Table 7: YVAM freeze damage protection requirements
Condition
Chiller control of chilled fluid circuit pumps
Waterbox immersion heaters
Ambient air temperatures from 32°F
(0°C) down to 0°F (-17.8°C)
Required
Not required
Ambient air temperatures below 0°F
(-17.8°C) down to -20°F (-28°C)
Required
Required
YVAM Control Center
28
Summary of Contents for YORK YVAM 0350
Page 2: ...2 YVAM Control Center...
Page 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Page 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Page 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Page 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Page 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Page 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Page 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Page 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Page 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...