Table 78: Programmable
Button
Description
Start
Access level required: Operator
Pressing this button clears the graph, starts a new graph, sets the time of day to the present
clock time, and begins the trending. This button is only available if trending is stopped. If
the selected chart type is Triggered and Trigger Action is set to Start, data collection will
not begin until the triggers have been satisfied and any selected trigger delay has elapsed.
Otherwise, data collection will begin immediately.
Stop
Access level required: Operator
Pressing this button stops the trending. The trend data is frozen on the display until another
graph is started with the Start button. The Stop button is only available if trending is
running.
Allows the data on the trend screen to be printed in tabular format. If set to Existing, a
snapshot of the data presently on the screen is sent to the printer. If set to New, all data
collected after pressing this button will be sent to the printer as it is collected. If set to
Disabled, no data is sent to the printer. See
for printout examples.
Data Select
Allows the user to display all trended data points simultaneously or select a single trended
data point for display, hiding the other data points. Selections are All Data or Data Point X
(1-6).
Y-Axis
This button toggles the Y-Axis labels of the graph. Each button press changes the label to
another of the selected parameters.
X-Axis
This button toggles the X-Axis labels of the graph. Each button press alternates the scaling
between time of day and elapsed time. The Time of Day scaling is in 24-hour format. The
Elapsed Time scaling is the time elapsed since the Start button was pressed, starting the
trending.
Table 79: Navigation
Button
Description
Home
Returns to the Home screen.
History
Returns to the History screen.
Trend Setup
Access level required: Operator
Only displayed if the trending is stopped. Causes a jump to a subscreen for configuring the
trending display.
YVAM Control Center
78
Summary of Contents for YORK YVAM 0350
Page 2: ...2 YVAM Control Center...
Page 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Page 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Page 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Page 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Page 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Page 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Page 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Page 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Page 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...