Surge screen
Figure 19: Surge screen overview
This screen displays the chiller compressor and all parameters relating to the surge protection
feature. All setpoints relating to this screen are maintained on this screen.
Table 26: Display only fields
Field/LED name
Description
Delta P/P
A parameter that represents the system differential or head pressure. It is calculated as
condenser pressure – evaporator pressure) / evaporator pressure
.
Surge Window Time
When the chiller enters run mode, this value counts up to the time programmed as the
Count Window setpoint. When it reaches the Count Window minutes, the number of surge
events in the oldest minute is discarded and the number of surge events in the most recent
minute is added. This provides a rolling count of the total surge events that have occurred in
the last Count Window minutes. This value is reset when the chiller shuts down.
Surge Window Count
Displays the number of surge events that have occurred in the last 1 to 5 minutes as
programmed with the Count Window setpoint. If the chiller has been running for less than
the Count Window minutes, it is the number of surge events that have occurred within the
last number of minutes displayed as the Surge Window Time. The count is cleared when the
chiller shuts down.
Surge Detected (LED)
Illuminates momentarily when a surge is detected by the surge protection feature.
Surge Count
Total number of surges accumulated by the surge protection feature.
Use the surge protection feature to define how many surges are excessive and how the control
reacts to an excess surge condition. When excess surging is detected, you can configure the chiller
to shut down. The sensitivity of this surge detection is set by the Sensitivity setpoint on this screen.
YVAM Control Center
46
Summary of Contents for YORK YVAM 0350
Page 2: ...2 YVAM Control Center...
Page 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Page 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Page 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Page 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Page 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Page 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Page 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Page 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Page 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...