Surge protection
The surge protection feature detects surge events. It provides a running count of the surges
detected over the lifetime of the chiller. It allows the user to define how many surges are excessive
and how the control reacts to an excess surge condition. When excessive surging is detected, this
feature can shut down the chiller.
Surge events are detected by monitoring the relationship between the condenser pressure
and evaporator pressure while the chiller is running. An excess surge condition is detected by
comparing the number of surge events that occur in a selectable time period to a selectable
threshold.
If the number of surge events (Surge Window Count) detected in the time period programmed
as the Count Window setpoint (1 minute to 5 minutes, default 5 minutes) exceed the threshold
programmed as the Count Limit setpoint (4 to 20, default 4), an excess surge condition has been
detected.
Unless the Shutdown features have been enabled, the chiller continues to operate under the same
conditions, displaying
WARNING – EXCESS SURGE DETECTED
. This message is displayed until it is
manually reset with the Warning Reset button in Operator access level. If the Shutdown setpoint
is enabled, when an excess surge condition is detected, a safety shutdown is performed and the
message
SURGE PROTECTION - EXCESS SURGE
appears.
21
YVAM Control Center
Summary of Contents for YORK YVAM 0350
Page 2: ...2 YVAM Control Center...
Page 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Page 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Page 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Page 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Page 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Page 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Page 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Page 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Page 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...