Table 11: Programmable
Button
Access
Description
Clear Fault
View
When safety conditions are detected, the chiller shuts down, and the main status
display of the chiller displays a message to indicate the cause of the shutdown. Use
this button to clear the fault and message after the condition is removed. The button
only shows when the condition can be cleared. If the chiller has a standing Local or
Remote run command, it starts when the button is pressed.
Warning Reset
Operator
Use this button to acknowledges a warning condition and reset the message display
associated with it.
Start
Operator
This button is only available when the chiller does not have a local run request. Press
this button to select Enter to run or Cancel to abort to stopped. If you press Enter, the
chiller starts if the control source is local, or runs if control source is any remote.
Soft Stop
Operator
This button is only available when the chiller is in local mode and has a local run
request. It shows in place of the Start button. Press this button to select Enter to stop
or Cancel to remain running. If you press Enter, the chiller performs a soft shutdown
and disables the remote run permissive.
Table 12: Navigation
Button
Description
System
This screen provides additional system information.
Evaporator
This screen provides a detailed view of all evaporator parameters, including the
programmable Leaving Chilled Liquid setpoints.
Condenser
This screen provides a detailed view of all condenser parameters, including control of the
liquid level functions.
Compressor
This screen provides a detailed view of all the compressor parameters. This includes surge
protection, MBC, variable geometry diffuser (VGD), and calibration.
Capacity Control
This screen provides a detailed view of all the parameters associated with capacity control.
VSD
This screen provides a detailed view of the motor and variable speed drive parameters. This
allows programming of the Current Limit and the Pulldown Demand Limit values.
Setpoints
This screen provides a single location to program the most common system setpoints. It
is also the gateway to many of the general system setup parameters such as Date/Time,
Display Units, Scheduling, Printer Setup, and similar parameters.
History
This screen provides access to a snapshot of system data at each of the last 10 shutdown
conditions, and provides for trending operating parameters.
35
YVAM Control Center
Summary of Contents for YORK YVAM 0350
Page 2: ...2 YVAM Control Center...
Page 10: ...Figure 4 Variable speed drive nomenclature YVAM Control Center 10...
Page 15: ...Figure 8 System piping and instrumentation diagram P ID 15 YVAM Control Center...
Page 154: ...Figure 62 Sample printout status or history YVAM Control Center 154...
Page 155: ...Figure 63 Sample printout status or history continued 155 YVAM Control Center...
Page 156: ...Figure 64 Sample printout setpoints YVAM Control Center 156...
Page 157: ...Figure 65 Sample printout setpoints continued 157 YVAM Control Center...
Page 158: ...Figure 66 Sample printout schedule YVAM Control Center 158...
Page 159: ...Figure 67 Sample printout sales order 159 YVAM Control Center...
Page 160: ...Figure 68 Sample printout security log report YVAM Control Center 160...