Table 2: Small direct fired absorption chiller-heater commissioning data sheet (2/3)
Combustion data
Measured by
Specification
Standard
Low
Middle
High
Output Value
%
Control panel
Fuel Damper
Position
%
Damper pointer
Air Damper
Position
%
Damper pointer
Fuel Primary
Pressure (P1)
Pressure gauge
Fuel Secondary
Pressure (P2)
Pressure gauge
Fuel Consumption
(see notes)
ft
3
/h
Flow meter
Fuel consumption
(see notes)
ft
3
N/h
Calculation
or flow meter
Exhaust Gas O
2
Concentration
%
Exhaust gas
analyzer
4.0~8.0
Exhaust Gas CO
Concentration
ppm
Exhaust gas
analyzer
≤100
Exhaust Gas CO
2
Concentration
%
Exhaust gas
analyzer
Exhaust gas NOx
concentration
ppm
Exhaust gas
analyzer
Wind Box
Pressure
Water
manometer
Draft Pressure
(P3)
Water
manometer
0~197.91 in WC
Furnace Pressure
(P4)
Water
manometer
Flame Current
μA
Flame
current meter
≥2.0
Burner Fan
Operation
Current
A
Cramp meter
Exhaust Gas
Temperature
°F
Control panel
≤482
Note:
If gas flow rate is taken as m
3
/h, calculate m
3
N/h with fuel pressure and ambient temperature.
Ambient temperature:
°F
YHAU-CGN/H-CXR(M) Small Direct Fired Absorption Chiller-Heater Checklist