Table 15: Contact specifications
Contact specification
Digital signal
Max. start and stop voltage: AC250 V/DC30
V
Max start and stop current: 2 A/1 point
(resistance load)
Max start and stop voltage: AC250 V/DC30
V (resistance load)
Absorption chiller-heater control panel
-> External input terminal
Analog signal
Permit resistance load: 500 Ω
Cooling water flow signal
4 mA:50% flow, 20 mA:100% flow
Digital signal Rated voltage/current: DC24 V; 7 mA
External output terminal -> Absorption
chiller-heater control panel
Analog signal
Chilled or hot water outlet temperature
remote signal (cooling)
4 mA: Setting base temperature
20mA: Setting base tempe remote
setting differential (heating)
4 mA: Setting base temperature
20mA: Setting base temperature - remote
setting differential
Figure 41: Remote stop and start signal
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater