Handling, storage, installation, and reassembly
Figure 7: Warning
DANGER
Rigging and lifting must be done by a professional rigger in accordance with a written rigging and
lifting plan. The most appropriate rigging and lifting method depends on job specific factors, such as
the rigging equipment available and site needs. A professional rigger must determine the rigging and
lifting method to be used. It is beyond the scope of this manual to specify rigging and lifting details.
CAUTION
This unit cannot be lifted or moved using a forklift.
This chiller-heater is for air conditioning or a cooling manufacturing process. Transport, store, and
use this chiller-heater under the following conditions:
Installation location:
Indoor, non-explosion area
Ambient temperature:
50~104°F (10 ~ 40°C)
Humidity:
10 ~ 90% (RH%)
Altitude:
3333 ft (1000 m) or lower
If the plant room temperature falls below 50°F (10°C), you must have the cold ambient option.
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater
20