Figure 74: Changeover valve locations for simultaneous operation
Table 31: Changeover valve operation/location for unit with auxiliary heat exchanger
Valve operation/location
Operation mode
HG -> LG
ref (VA)
E -> A (VB)
HG sol
supply (V3)
HG sol
return (V2)
Purging valve
CW valve
CH valve
HW valve
Cooling
Open
Close
Open
Open
Open: VC, V15,
VB close
Inlet/outlet open Inlet/outlet open
Inlet: Close;
Outlet: Open
slightly
Heating
Close
Open
Close
Close
Close: V15,V16.
VD opens 30
seconds when
necessary
Inlet: Close;
Outlet: Open
slightly
Inlet: Close;
Outlet: Open
slightly
Inlet/outlet open
Simultaneous
Open
Close
Open
Open
Open: VC, V15,
VB close
Inlet/outlet open Inlet/outlet open Inlet/outlet open
143
Model YHAU-CGN/H-CXR(M)Double Effect Direct Fired Small Absorption Chiller-Heater