Setting scope and default of the parameter
START CONDITION 100~300% Default
:
120%
STOP CONDITION 100~300% Default
:
150%
Parameter setting instruction:
START CONDITION
:
When a system is running, the
conditions to start another system.
STOP CONDITION
:
When the two systems running at
the same time, the conditions for the turn off a system.
(16) Parameter Setting Interface-16
Press F1 to return to the parameter setting interface-3
Press F2 to modify the signs of parameter setting
Press F3 to return to the previous setting interface
Press F4 to enter into the next parameter setting interface
START/STOP MODE AUTO
CONTROL MODE MODBUS
ECL OFFSET 0.0
℃
LCL OFFSET 0.0
℃
SYS1 FLA 111.0 A
SYS2 FLA 111.0 A
MODEL YEWS200DA53D
BYPASS VALVE DLY 15S
RETU
+/-
NEXT
BACK
Setting scope and default of the parameter
START/STOP MODE MANUAL/AUTO Default:MANUAL
CONTROL MODE LOCAL/REMOTE/MODBUS Default: LOCAL
ECL OFFSET -5.0 ~ +5.0
℃
Default: 0.0
℃
LCL OFFSET -5.0 ~ +5.0
℃
Default: 0.0
℃
SYS1 FLA
60.0 ~ 400.0 A
Default: 111.0 A
SYS2 FLA
60.0 ~ 400.0 A
Default: 111.0 A
BYPASS VALVE DLY: 5~60 sec
Default: 15sec
Parameter setting instruction:
START/STOP MODE
:
When set as
MANUAL
, the
unit will operate according to the keys on the control
panel or remote switch, or perform the switch control in
Modbus protocol. If set as
AUTO
switch, the set time for
startup and stop of the unit will control the startup and
stop operations.
CONTROL MODE
:
If set as
LOCAL
, the startup and
stop will be completed by the operation panel, if set as
REMOTE
, the startup and stop will be realized by DI
YEWS-E Water Cooling Screw Chiller/Heat Pump
priority system to start, if the start priority is set to
System1, the system1 is always a priority in the system2
to start . Only in the
USE ONE SYSTEM
set up for
DUAL
, this setting be useful.
USE ONE SYSTEM
:
Dual-system units, in some
cases wish to start a system, another system is not
running. The default case, the two systems can be
running. If the
USE ONE SYSTEM
is set to
SYS1
, then
only system 1 is running, the system2 does not run; if the
USE ONE SYSTEM
is set to
SYS2
, then only the
System2 is running, the system1 does not run; if the
USE ONE SYSTEM
is set to
DUAL
, the system1 and
system2 can be running. Only by
USE ONE SYSTEM
set up for
DUA
L,
START
PRIORITY
is used, otherwise non-functional.
OIL PREHEAT
:
In some cases the need for debug-
ging start unit, if the use of oil pre-heating will affect the
debugging process. Therefore, through the
OIL
PREHEAT
will be set to
NO
, temporarily masked the
oil preheating function.When the debugger has finis-
hed,the
OIL PREHEAT
must be set to
YES
.
START PRIORITY
and
USE ONE SYSTEM
,
Only
in the use of dual-system units, units in a single system
does not use. These parameters should be setting in the
two systems are in the case of stop.
(15) Parameter Setting Interface-15
Press F1 to return to the parameter setting interface-3
Press F2 to modify the signs of parameter setting
Press F3 to return to the previous setting interface
Press F4 to enter into the next parameter setting interface
START CONDITION: 150%
STOP CONDITION: 150%
BACK
NEXT
RETU
36
Summary of Contents for YEWS Series
Page 79: ...YEWS electrical drawing compressor for 50Hz power 74...
Page 80: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H 210H for 50Hz power 75...
Page 81: ...YEWSelectrical drawing main board YEWS215P for 50Hz power 76...
Page 82: ...77 YEWS electrical drawing Main Board YEWS100P 130P 170P 200P for 50Hz power...
Page 83: ...YEWS electrical drawing compressor for 60Hz power 78...
Page 84: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H for 60Hz power 79...
Page 85: ...YEWS electrical drawing main board YEWS215P for 60Hz power 80...
Page 86: ...YEWS field connection for 60Hz power 81...
Page 87: ...Transformer for230V 3P 60Hz Application 82...
Page 88: ...Form No AP1105 IOM01 1216 EN Supersedes AP1105 IOM01 0316 EN...