Instructions for capacity control (AC mode for example)
Ts
:
Leaving chilled water temperature setpoint (LEL TEMP SET )
D
:
Differential of Leaving chilled water temperature (LEL TEMP CR)
Db
:
Differential buffering value
When leaving chilled water temperature
≥
(Ts + D), the compressor will load. when leaving chilled water
temperature
≥
(Ts - D) and
≤
(Ts + D) , the comrepssor will operate fuzzy control logic. when leaving chilled
water temperature
≥
(Ts
–
D- Db) and
≤
(Ts - D) , the comrepssor will unload. When leaving chilled water
temperature
≤
(Ts
–
D- Db) , the compressor will be cycling shut down.
By setting the value of Ts, D and Db, the temperature range of different running
mode(Hold/Unload/Load/Stop) of compressor can be adjusted.
Loading
Holding
Unloading
Emergency Stop
Low
temperature
High
temperature
Ts+D
Ts
Ts-D
Ts-D-Db
YEWS-E Water Cooling Screw Chiller/Heat Pump
32
Summary of Contents for YEWS Series
Page 79: ...YEWS electrical drawing compressor for 50Hz power 74...
Page 80: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H 210H for 50Hz power 75...
Page 81: ...YEWSelectrical drawing main board YEWS215P for 50Hz power 76...
Page 82: ...77 YEWS electrical drawing Main Board YEWS100P 130P 170P 200P for 50Hz power...
Page 83: ...YEWS electrical drawing compressor for 60Hz power 78...
Page 84: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H for 60Hz power 79...
Page 85: ...YEWS electrical drawing main board YEWS215P for 60Hz power 80...
Page 86: ...YEWS field connection for 60Hz power 81...
Page 87: ...Transformer for230V 3P 60Hz Application 82...
Page 88: ...Form No AP1105 IOM01 1216 EN Supersedes AP1105 IOM01 0316 EN...