12 DECOMMISSIONING,DISMANTLING AND DISPOSAL
12.1 General description
Never release refrigerant to the atmosphere when
emptying the refrigerating circuits. Suitable
retrieval equipment must be used. If reclaimed
refrigerant cannot be reused. It must be
Enteringed to the manufacturer.
Never discard used compressor oil, as it contains
refrigerant in solution. Entering used oil to the
oil manufacturer.
Unless otherwise indicated, the operations described bel-
ow can be performed by any properly trained mainten-
ance technician.
Isolate all sources of electrical supply to the unit including
any control system supplies switched by the unit. Ensure
that all points of isolation are secured in the 'OFF'
position. The supply cables may then be disconnected and
removed. For connection points refer to Section 4.
Remove all refrigerant from each system of the unit into a
suitable container using a refrigerant reclaim or recovery
unit.This refrigenmt may then be re-used, if appropriate,
or Enteringed to the manufacturer for disposal. Under NO
circumstances should refrigerant be vented to atmosphere.
Drain the oil from each system into a suitable container
and dispose of according to local laws and regulations
governing the disposal of oily wastes. Any spill oil should
be mopped up and similarly disposed of.
Isolate the unit heat exchangers from the external water
systems and drain the heat exchanger section of the
systems. If no isolation valves are installed it may be
necessary to drain the complete system.
After draining, the water pipework can be disconnected
and removed.
Units can generally be removed in one piece after
disconnection as above. Any mounting bolts should be
removed and then the unit should be lifted from position
using the points provided and equipment of adequate
lifting capacity.
Reference should be made to Section 4 for unit
installation instructions, Section 9 for unit weights and
Section 3 for handling.
Units which cannot be removed in one piece after
disconnection as above must be dismantled in position.
Special care should be taken regarding the weight and
handling of each component.Where possible units should
be dismantled in the reverse order of installation.
Residual refrigerant oil and glycol or similar
solutions may remain in some parts of the
system. These should be mopped up and
disposed of as described above.
It is important to ensure that whilst components are being
removed the remaining parts are supported in a safe
manner.
Only use lifting equipment of a dequate capacity.
After removal from position the unit parts may be
disposed of according to local laws and regulations.
WARNING
WARNING
WARNING
WARNING
YEWS-E Water Cooling Screw Chiller/Heat Pump
71
Summary of Contents for YEWS Series
Page 79: ...YEWS electrical drawing compressor for 50Hz power 74...
Page 80: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H 210H for 50Hz power 75...
Page 81: ...YEWSelectrical drawing main board YEWS215P for 50Hz power 76...
Page 82: ...77 YEWS electrical drawing Main Board YEWS100P 130P 170P 200P for 50Hz power...
Page 83: ...YEWS electrical drawing compressor for 60Hz power 78...
Page 84: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H for 60Hz power 79...
Page 85: ...YEWS electrical drawing main board YEWS215P for 60Hz power 80...
Page 86: ...YEWS field connection for 60Hz power 81...
Page 87: ...Transformer for230V 3P 60Hz Application 82...
Page 88: ...Form No AP1105 IOM01 1216 EN Supersedes AP1105 IOM01 0316 EN...