ECL OFFSET
LCL OFFSET
MODBUS ADDRESS
BATTERY BACKUP
PASSWORD
TIME LIMIT
LIMITED HOURS
START/STOP MODE
RUN MODE
CONTROL MODE
LOAD TIME
UNLOAD TIME
CONTR.CYCLE
MIN.RUN TIME
ANTI-RECYCLE
SYS1 FLA
SYS2 FLA
BYPASS VALVE DLY
START PRIORITY
USE ONE SYSTEM
OIL PREHEAT
SYS 1 RUN CTRL.
SYS 2 RUN CTRL.
SYS1 CUR.OFFSET
SYS2 CUR.OFFSET
CLEAR FAULT RECORD
RESET FAIL.
ANTIFREEZE
CLEAR RECORD
DEFAULT DATA
-5.0
–
+5.0
℃
-5.0
–
+5.0
℃
1
–
255
YES/NO
YES/NO
YES/NO
0
–
9998H
MANUAL/AUTO
AC/ITS/HP
LOCAL/REMOTE/MODBUS
0.5-20.0s
0.5-20.0s
5-60s
120-600s
120-600s
60.0 ~ 400.0 A
60.0 ~ 400.0 A
5
–
90 s
AUTO/SYS1/SYS2
DUAL/SYS1/SYS2
YES/NO
AUTO/LOAD/UNLOAD
AUTO/LOAD/UNLOAD
50
–
150 %
50
–
150 %
----/YES
----/SYS1/SYS2
YES/NO
----/SYS1/SYS2
----/YES
Service password
Service password
Service password
User password
Ex-factory password
Service password
Service password
User password
User password
User password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Ex-factory password
Service password
Service password
Service password
Service password
Service password
Service password
Service password
Ex-factory password
User password
Service password
Service password
Service password
5.5 General parameters setting and defult values
(1) Sharing parameters setting and defult values
0
℃
0
℃
1
NO
YES
NO
2100 H
MANUAL
AC
LOCAL
2.0s
4.5s
10s
300s
480s
111.0
111.0
15s
AUTO
DUAL
YES
AUTO
AUTO
100%
100%
----
----
YES
----
----
YEWS-E Water Cooling Screw Chiller/Heat Pump
40
Summary of Contents for YEWS Series
Page 79: ...YEWS electrical drawing compressor for 50Hz power 74...
Page 80: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H 210H for 50Hz power 75...
Page 81: ...YEWSelectrical drawing main board YEWS215P for 50Hz power 76...
Page 82: ...77 YEWS electrical drawing Main Board YEWS100P 130P 170P 200P for 50Hz power...
Page 83: ...YEWS electrical drawing compressor for 60Hz power 78...
Page 84: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H for 60Hz power 79...
Page 85: ...YEWS electrical drawing main board YEWS215P for 60Hz power 80...
Page 86: ...YEWS field connection for 60Hz power 81...
Page 87: ...Transformer for230V 3P 60Hz Application 82...
Page 88: ...Form No AP1105 IOM01 1216 EN Supersedes AP1105 IOM01 0316 EN...