The corresponding of concentrations and freezing points of glycol solution
E.G wt%
5
10
15
Freezing point
℃
-1.4
-3.28
-5.31
E.G wt%
20
26
30
Freezing piont
℃
-7.8
-11.38
-14.04
The saturated temperature of R134a in difference pressure
Pressure kpa
164
171
178
185
193
201
209
Saturated temperature
℃
-15
-14
-13
-12
-11
-10
-9
Pressure kpa
217
225
234
243
253
262
272
Saturated temperature
℃
-8
-7
-6
-5
-4
-3
-2
Pressure kpa
282
293
304
315
326
338
350
Saturated temperature
℃
-1
0
1
2
3
4
5
Flow Switch
Verify a chilled water flow switch is correctly fitted in the
,
customer s piping on the cooler outlet, and wired into the
control panel correctly using shielded cable.
Control panel pwer supply
Make sure that the control panel is power on and the
display screen can display normarly.
Programmed Options
Make sure all the options factory-programmed into the
Microprocessor Panel are in accordance with the cust-
,
omer s order requirements by pressing relevant Keys on
the keypad (Refer to instructions on the operation of
control System on section 5).
Programmed Settings
Make sure all the setpoints are in accordance with the
operating requirements by operating keypad (Refer to
instructions on the operation of control System on section
5).The setpoints of the chilled water temperature or hot
water temperature should be set according to the Unit
model and working conditions.
Time and Date
Setting the time/date by pressing relevant function Keys
on the keypad (Refer to instructions on the operation of
control System on section 5).
Startup/Stop arrangement
Setting the Startup/Stop arrangement in ordianary days
and holidays via the corresponding function keys.
(Refer to instructions on the operation of control System
on section 5).
Setpoints
Setting the setpoints and control range of the chilled/hot
water temperature(Refer to instructions on the operation
of control System on section 5).
Now the chiller is ready to work.
YEWS-E Water Cooling Screw Chiller/Heat Pump
50
Summary of Contents for YEWS Series
Page 79: ...YEWS electrical drawing compressor for 50Hz power 74...
Page 80: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H 210H for 50Hz power 75...
Page 81: ...YEWSelectrical drawing main board YEWS215P for 50Hz power 76...
Page 82: ...77 YEWS electrical drawing Main Board YEWS100P 130P 170P 200P for 50Hz power...
Page 83: ...YEWS electrical drawing compressor for 60Hz power 78...
Page 84: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H for 60Hz power 79...
Page 85: ...YEWS electrical drawing main board YEWS215P for 60Hz power 80...
Page 86: ...YEWS field connection for 60Hz power 81...
Page 87: ...Transformer for230V 3P 60Hz Application 82...
Page 88: ...Form No AP1105 IOM01 1216 EN Supersedes AP1105 IOM01 0316 EN...