SYS1 BYPASS CTRL.
:
If
SYS1 BYPASS CTRL
. is
set as
AUT
O, which should be controlled according to the
specific logic; while if
SYS1 BYPASS CTRL
. is set as
MANUAL
, it should be operated in accordance with the
BYPASS1
or
BYPASS1
.
(BYPASS just suit for the style before D1)
SYS2 BYPASS CTRL.
:
For system2,With the same
SYS1 BYPASS CTRL.
Single-system units, Settings of related to the system2
don
’
t use.
(4)Parameter Setting Interface-4
Press F1 to retur n t o th e paramete r settin g interface-1.
Press F2 to enter into the parameter setting interface of
AC mo de.
Press F3 to enter into the parameter setting interface of
ITS mode.
Press F4 to enter into the parameter setting interface of
HP mode.
LEL TEMP SET 7.0
℃
LEL TEMP CR 1.0
℃
CR BUFFER 2.5
℃
LOW LELT 2.0
℃
HIGH LCLT 43.0
℃
L E.P UNLOAD 175KPa
L E.P SHUTDOWN 165KPa
COOL SETTING
RETU
NEXT
MODE SETTING
COOL SETTING
ITS SETTING
HEAT(D1-HP/E-HP2) SETTING
RETU
NEXT
NEXT
NEXT
(5)Parameter Setting Interface-5
Press F1 to return to the parameter setting interface-3.
Press F4 to enter into the next parameter setting interface.
Setting scope and default value of the parameter
LEL TEMP SET: 4.0
℃
~15.0
℃
Default: 7.0
℃
LEL TEMP CR: 0.5
℃
~2.0
℃
Default: 1.0
℃
HIGH LCLT : 30.0
℃
~60.0
℃
Default: 43.0
℃
L E.P UNLOAD: 150~300kPa Default: 175kPa
L E.P SHUTDOWN: 150~300kPa Default: 165kPa
CR BUFFER
:
1.0
–
2.5
℃
Default: 2.5
℃
LOW LELT
:
1.0
–
7.0
℃
Default: 2.0
℃
Parameter setting instructions:
LEL TEMP SET: Set the desired leaving evaporator fluid
temperature, the default is 7.0
℃
LEL TEMP CR: Used to decide the desired fluid temp-
erature control range, the default is 1.0
℃
LOW LELT: If the leaving evaporator liquid temper-
ature
≤
LOW LELT setpoint, fault alarm will be
displayed and the compressor will be shut off, but the
water pump is still on runing. The Cycling Startup Logic
will be actived when the leaving chilled liquid
temperature
≥
(LOW LCLT se10.0
℃
).
HIGH LCLT
:
If the leaving condenser liquid temper-
ature
≥
HIGH LCLT setpoint, fault alarm will be
displayed and the compressor will be shut off, but the
water pump is still on runing. The Cycling Startup Logic
will be actived when the leaving cooling liquid
temperature
≤
(HIGH LCLT temperature setpoint -
10.0
℃
).
L E.P UNLOAD: If the evaporator pressure
≤
L E.P
UNLOAD setpoint, the compressor will unload
compulsively,the unit will come back to normal capacity
control when the evaporator pressure
≥
(L E.P UNLOAD
s25Kpa ). Default L E.P UNLOAD setpoint is
175kPa.
L E.P SHUTDOWN: If the evaporator pressure
≤
L E.P
SHUTDOWN setpoint, the unit will stop immediately.
Default L E.P SHUTDOWN setponit is 165 kPa.
The control method of units in ITS/HP mode is the same
as those in AC mode, but the setpoints are different with
different working mode.
YEWS-E Water Cooling Screw Chiller/Heat Pump
HEAT(E-HP) SETTING
31
Summary of Contents for YEWS Series
Page 79: ...YEWS electrical drawing compressor for 50Hz power 74...
Page 80: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H 210H for 50Hz power 75...
Page 81: ...YEWSelectrical drawing main board YEWS215P for 50Hz power 76...
Page 82: ...77 YEWS electrical drawing Main Board YEWS100P 130P 170P 200P for 50Hz power...
Page 83: ...YEWS electrical drawing compressor for 60Hz power 78...
Page 84: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H for 60Hz power 79...
Page 85: ...YEWS electrical drawing main board YEWS215P for 60Hz power 80...
Page 86: ...YEWS field connection for 60Hz power 81...
Page 87: ...Transformer for230V 3P 60Hz Application 82...
Page 88: ...Form No AP1105 IOM01 1216 EN Supersedes AP1105 IOM01 0316 EN...