5.4.2 Home Interface
On the home interface:
Pressing the
F1
to
F4
key will enter into 4 sub-interfaces
of
“
INFO
” “
SET
” “
TIME
”
and
“
FAIL
”
separately.
The first line of the main interface will display the current
date and time.
LCL/LHL:
In AC and ITS mode, it's the leaving
condenser cooling liquid temperature. In heap-pump
mode, it's the leaving condenser hot water temperature is
displayed, which should be regarded as the control
reference in HP mode..
ECL/EHL:
In AC and ITS mode, it's the enter condenser
cooling liquid temperature. In heap-pump mode, it's the
enter condenser hot water temperature is displayed.
LEL:
Leaving evaporator liquid temperature, which
should be regarded as the control reference in AC&ITS
mode.
WELCOME TO USE YORKCHILLER
YEWS Screw chiller
INFO
SET
TIME
FAIL
HEAT
2 0 0 6 / 0 0 / 0 0 0 0 : 0 0 : 0 0 S a t
5.4 Instructions of Display Interface
5.4.1 Initialization Interface
A JOHNSON CONTROLS COMPANY
OFF
MODE
OPH
LHL
ENL
LIMT
LEL
EEL
COMM. SYS1 ON SYS2 ON 01#
UNIT TYPE AC UNIT
COMP STA LOW DISH HOLD
SAT.EVAP.T
SAT.DIS.T
DIS.SUPERHEAT
UL.COEF,
ANTI-RECYC TIMELEFT 100S
25.0
℃
25.0
℃
25.0
℃
100.0%
RETU
NEXT
18.0
^
C
18.0
^
C
18.0
^
C
18.0
^
C
EEL:Entering
evaporator liquid temperature.
MODE:
Current operation mode of the unit
ON/OFF:
Display the startup and stop status, which
should be displayed as ON when unit is running, and be
displayed as OFF while unit is standby.
OPH&LIMT:
Flash display the unit status, no display if
there is no relevant operation status.
FAIL:
Flash diaplay if there is fault, no display if without
fault.
The start and stop operation can only be done on the
home interface.
5.4.3 Status Display
In the home interface, enter into the display interface
upon pressing
F1 key
, while in the display interface, the
operation instructions for the keys are as follows:
(1) Status display interface-1
Press F1 to return to the main interface.
Press F4 to enter into the next display interface.
COMM.STATUS:
If the communication between the ce-
ntralized controller and 1# main board is normal,
SYS1
ON
will be displayed, otherwise,
SYS1 OFF
will be dis-
played. If the communication between the centralized
controller and 2# main board is normal,
SYS2 ON
will be
displayed,otherwise,
SYS2 OFF
will be displayed.In sin-
gle compressor unit,
SYS2 OFF
always be displayed.
In
single compressor unit,SYS1 ON only be used
.
YEWS-E Water Cooling Screw Chiller/Heat Pump
25
Summary of Contents for YEWS Series
Page 79: ...YEWS electrical drawing compressor for 50Hz power 74...
Page 80: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H 210H for 50Hz power 75...
Page 81: ...YEWSelectrical drawing main board YEWS215P for 50Hz power 76...
Page 82: ...77 YEWS electrical drawing Main Board YEWS100P 130P 170P 200P for 50Hz power...
Page 83: ...YEWS electrical drawing compressor for 60Hz power 78...
Page 84: ...YEWS electrical drawing main board YEWS100H 130H 170H 200H for 60Hz power 79...
Page 85: ...YEWS electrical drawing main board YEWS215P for 60Hz power 80...
Page 86: ...YEWS field connection for 60Hz power 81...
Page 87: ...Transformer for230V 3P 60Hz Application 82...
Page 88: ...Form No AP1105 IOM01 1216 EN Supersedes AP1105 IOM01 0316 EN...