TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
32
Compressor Interlock
BV 86
0 = Off
1 = On
TEC2602-address
8
Device 76aaa
9
TEC2602-4 to TEC2602-127
1.
This MS/TP Bus object is readable and only writable if the corresponding override is set. (For
example,
Room Temp
has a corresponding override object of
Room Temp Override
. This
corresponding override object needs to be set to
1 = Override
to be able to write
Room Temp
to a
different value.)
2.
This MS/TP Bus object is readable and writable.
3.
This MS/TP Bus object may automatically release after 10 minutes with no BACnet traffic.
4.
This MS/TP Bus object is readable and only writable when out of service.
5.
This BI object type status is available even if the configuration is set to
None
.
6.
This MS/TP Bus object requires that
Frost Protection
be set to
1 = On
.
7.
If one setpoint of a pair of heating and cooling setpoints (for example,
Occupied Heat Setpoint
and
Occupied Cool Setpoint
) is overridden, the other setpoint of the pair may be automatically adjusted
by the thermostat controller to maintain the minimum deadband between the two setpoints.
8.
The address range actually displays from
0
to
254
. Only choose an address within the
4
to
127
range.
9.
The designation
aaa
is the address of the device (from
004
to
127
) on the MS/TP network.
Table 7: TEC2602-4 and TEC2602-4+PIR MS/TP Bus Objects (Part 4 of 4)
Point Name
Thermostat Point
(Type/Address)
Range