TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
14
BI1 Configuration
MSV 46
1 = None
2 = Rem NSB
3 = Motion NO
4 = Motion NC
5 = Window
BI2 Configuration
MSV 47
1 = None
2 = Door Dry
3 = Override
4 = Filter
5 = Service
UI3 Configuration
MSV 48
1 = None
2 = COC/NH
3 = COC/NC
4 = COS
5 = SS
Menu Scroll
BV 49
0 = No Scroll
1 = Scroll Active
BV 50
0 = Disabled
1 = Enabled
Temperature Scale
BV 51
0 = °C
1 = °F
Pipe Number (BO1 and BO2)
Configuration
MSV 52
1 = Two-Pipe
2 = Four-Pipe
AUX (BO5) Configuration
MSV 54
1 = Not Used
2 = NO with Occ
3 = NC with Occ
4 = NO with Occ and Fan
5 = NC with Occ and Fan
6 = Networked Controlled
Password Value
AV 56
0 to 1,000
Fan Mode Sequence
MSV 57
1 = Low-Med-High
2 = Low-High
3 = Low-Med-High-Auto
4 = Low-High-Auto
5 = On-Auto
Heating Setpoint Limit
AV 58
40.0°F/4.5°C to
90.0°F/32.0°C
Cooling Setpoint Limit
AV 59
54.0°F/12.0°C to
100.0°F/37.5°C
Setpoint Type
BV 60
0 = Permanent
1 = Temporary
Setpoint Function
BV 61
0 = Dual Setpoints
1 = Attached Setpoints
Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects